Understanding shortfalls

The criticality analysis works by identifying the shortfalls that occur when a segment is taken out of service. Depending on the type of analysis, different indicators of shortfall (i.e. drop in system performance) are used. The types of indicators of shortfall for each type of analysis are summarized in the table below.

Run with Hydraulic Engine PDD? Steady State/EPS Flow Results Pressure Results
No N/A N/A No flow if not connected N/A
Yes No EPS No flow if not connected Max Pressure Drop
Yes No Steady State No flow if not connected Max Pressure Drop
Yes Yes EPS Volume reduction Max Pressure Drop
Yes Yes Steady State Flow Reduction Max Pressure Drop